TIMER_NOT_DRIVEN¶
Severity: warn
A timer instance's .Q or .ET output is read elsewhere in the POU,
but no call site for that instance has an IN named argument.
Why it matters. A common pattern bug, the timer is called once
without IN, then Q is sampled. Q stays at its initial value
forever; the surrounding logic silently misfires.
Settings. No check-specific config.
Trigger.
The bot posts.
🟧 warn TIMER_NOT_DRIVEN
Timer T1 (TON) has its Q/ET read but no call sets IN
The timer is invoked but never with a named `IN := ...` argument.
Q will stay at its initial value.
Fix. Add IN := <condition> to the timer call.