TIMER_PT_ZERO¶
Severity: error
A TON / TOF / TP is set with PT := T#0s, or a constant that
resolves to zero.
Why it matters. PT = 0 fires immediately on TON / TP (the
delay is zero) or never on TOF (the off-delay is zero). Almost
always the wrong intent.
Settings. No check-specific config.
Trigger.
The bot posts.
🟥 error TIMER_PT_ZERO
Timer T1.PT resolves to T#0s (value: T#0s)
A PT of zero either fires immediately (TON/TP) or never (TOF on
falling edge), neither of which is usually intended.
Fix. Set a non-zero PT.